 Wiring/Electrical Generator Question 
Author Message
MMT Pro Member
User avatar

Joined: Sun Jun 17, 2012 1:30 pm
Posts: 425
Location: Houma, LA
Post Wiring/Electrical Generator Question
Random question here but pretty confident a few on here would have the answer..

So I am wiring up a small floating camp, the breaker panel will only have (2) 20amp breakers. I have 2 generators, one has a L5-30 (120) plug and the larger generator has a L14-30 (120/240).

My plan is to install a L14-30 inlet power box and wire it to my breaker panel. However I also want the option to power the camp with the smaller generator that has the L5-30 plug. I plan on getting an adapter so this will plug into the L14-30 power inlet box.

So here's my question. Will I have to change the way the breaker box is wired when switching between the two or will it not make any difference and supply both 20 amp breakers no problem?

Thanks

_________________
1944 skiff with 35 GTR


Thu Sep 05, 2013 6:50 pm
Profile
MMT 1000 Club
User avatar

Joined: Sun Jan 29, 2012 9:15 pm
Posts: 2552
Post Re: Wiring/Electrical Generator Question
The breakers on inside will protect from over load. And i sure the genset has a breaker to protect out put if it is to much. Are both the plug ins on each genset the same?

_________________
17/54 gator tail extreme with a stage 2 gator tail strapped on the back

viewtopic.php?f=5&t=43412


Thu Sep 05, 2013 6:59 pm
Profile
MMT 1000 Club
User avatar

Joined: Sun Nov 01, 2009 6:25 pm
Posts: 1935
Location: Kaufman- TEXAS
Post Re: Wiring/Electrical Generator Question
Volts is volts
Amps is amps

If gen a is running 120v at 30 amps
And gen b is running the same your good

Can't switch 120/240


Thu Sep 05, 2013 7:00 pm
Profile
MMT 1000 Club
User avatar

Joined: Sun Nov 01, 2009 6:25 pm
Posts: 1935
Location: Kaufman- TEXAS
Post Re: Wiring/Electrical Generator Question
Double bubble


Thu Sep 05, 2013 7:00 pm
Profile
MMT Pro Member

Joined: Wed Jul 24, 2013 9:16 pm
Posts: 232
Location: Deep East Texas
Post Re: Wiring/Electrical Generator Question
A standard breaker box is set up to accept a 240v input (2- 120v lines), in order to accept your 120v power source from the little genset, you will need both of your breakers on the same "leg" in the breaker box, otherwise you are going to have power to 1 breaker, but not the other when using the smaller genset (you will have to make both breakers feed from the same source). This also means your 20A breakers in the box will actually be protecting a potential 40A total load for the 2 breakers.

You can overcome the "leg" problem with the addition of a 3rd breaker, but it starts to become a little complicated...

_________________
The key to a successful marriage?
Give a man a 4X4 truck, a rifle, a shotgun, a Mud boat, and a fishing pole - he will be out of your hair most of the year...


Thu Sep 05, 2013 8:59 pm
Profile
MMT Pro Member
User avatar

Joined: Sun Jun 17, 2012 1:30 pm
Posts: 425
Location: Houma, LA
Post Re: Wiring/Electrical Generator Question

_________________
1944 skiff with 35 GTR


Fri Sep 06, 2013 2:45 am
Profile
MMT Pro Member
User avatar

Joined: Sun Jun 17, 2012 1:30 pm
Posts: 425
Location: Houma, LA
Post Re: Wiring/Electrical Generator Question
Or would it make more sense to just install a single 30A breaker so it will run off both gensets with no concern over the leg issues..?

_________________
1944 skiff with 35 GTR


Fri Sep 06, 2013 4:05 am
Profile
MMT Addict

Joined: Wed Oct 03, 2012 6:50 am
Posts: 565
Location: Union, LA
Post Re: Wiring/Electrical Generator Question
I'd have a friend that's an electrician to come look

Sent from my iPad using Tapatalk HD


Fri Sep 06, 2013 4:09 am
Profile
MMT Pro Member

Joined: Wed Jul 24, 2013 9:16 pm
Posts: 232
Location: Deep East Texas
Post Re: Wiring/Electrical Generator Question
This is the most explanatory diagram I could find:
Inside-Main-Breaker-Box-800.jpg

On a standard breaker box, you have (2) 120V main lines (240V total) - each 1 is a "leg" or phase. In order for the breaker box to be able to produce an OUTPUT breaker of 240V these "legs" have to be staggered inside the breaker box on what is called the bus bar. Since they are staggered, if you have (2) 120v breakers side by side, you are actually using (1) of each of the bus bars (or legs).

So, if you are going to use your 120V genset the breakers will need to feed from the same "leg" in the breaker box - 120V is only a single wire. You can put 2 breakers in the panel on the same leg (bus bar) to run your load, but you will not be getting the full potential from your 240V genset.

Going with a 30A single breaker defeats the protection of the circuit breaker in the panel, as you will trip your little genset before the breaker in the panel trips.

In order to use the 240V genset to it's potential, as well as being able to use the 120V genset, you will need 3 breakers in the panel (and you are going to need to make sure the 120V genset plug is wired to power up bus bar A) - Call these breakers #1, #2, & #3 - Breaker #1 (bus bar A) will feed what ever load in the camp you are putting on it, breakers #2 (bus bar B) & #3 (bus bar A) will be dedicated for the 2nd load. Breaker #2 will feed the other load in the camp, but you are going to need to put a jumper wire from the OUTPUT of breaker #2 to the OUTPUT of breaker #3 as well. When you use the 240V genset, breakers #1 & #2 will be ON (#3 [bus bar A] will be turned OFF), when using the 120V genset, breakers #1 and #3 will be ON (#2 [bus bar B] will be turned OFF)


You do not have the required permissions to view the files attached to this post.

_________________
The key to a successful marriage?
Give a man a 4X4 truck, a rifle, a shotgun, a Mud boat, and a fishing pole - he will be out of your hair most of the year...


Fri Sep 06, 2013 6:43 am
Profile
MMT Addict
User avatar

Joined: Mon Jan 19, 2009 5:22 am
Posts: 535
Location: New Orleans
Post Re: Wiring/Electrical Generator Question
I have all 110 in my camp. I also run a small generator in the winter. I have a jumper cable made up with two standard three prong males to a single female twist lock 220. Powers both legs in my box but this only works if there is no option to accidentally run a 220 item. The reason my camp is all 110, even the water heater.

_________________
17' CAT 5 with 37 GTR


Fri Sep 06, 2013 7:36 am
Profile
MMT Pro Member
User avatar

Joined: Sun Jun 17, 2012 1:30 pm
Posts: 425
Location: Houma, LA
Post Re: Wiring/Electrical Generator Question

_________________
1944 skiff with 35 GTR


Fri Sep 06, 2013 12:17 pm
Profile
MMT Addict
User avatar

Joined: Mon Jan 19, 2009 5:22 am
Posts: 535
Location: New Orleans
Post Re: Wiring/Electrical Generator Question
IMO way too much drinking goes on at camps to have the above setup that allows the two legs to be combined with the flip of a switch. I assume your 110 generator has in addition to the twist lock you describe, standard three prong grounded female connections. What I describe is simple and as long as you have no 220 loads basically foolproof.

_________________
17' CAT 5 with 37 GTR


Fri Sep 06, 2013 4:46 pm
Profile
MMT Pro Member

Joined: Wed Jul 24, 2013 9:16 pm
Posts: 232
Location: Deep East Texas
Post Re: Wiring/Electrical Generator Question


You do not have the required permissions to view the files attached to this post.

_________________
The key to a successful marriage?
Give a man a 4X4 truck, a rifle, a shotgun, a Mud boat, and a fishing pole - he will be out of your hair most of the year...


Fri Sep 06, 2013 6:18 pm
Profile
MMT Pro Member
User avatar

Joined: Sun Jun 17, 2012 1:30 pm
Posts: 425
Location: Houma, LA
Post Re: Wiring/Electrical Generator Question

_________________
1944 skiff with 35 GTR


Fri Sep 06, 2013 6:46 pm
Profile
Display posts from previous:  Sort by  
Reply to topic   [ 14 posts ] 

Who is online

Users browsing this forum: Google [Bot] and 1 guest


You cannot post new topics in this forum
You cannot reply to topics in this forum
You cannot edit your posts in this forum
You cannot delete your posts in this forum
You cannot post attachments in this forum

Jump to: